Gira has introduced new switch actuators for KNX. The DIN-rail devices switch lighting, sockets and other loads, in homes as well as commercial buildings. There are twelve versions with 2 to 24 channels, each for 10 or 16 amps. All of them support KNX Secure. According to Gira, they are available now.
New to KNX? Switch actuators sit in the distribution board and switch the circuits, while push buttons and sensors send them commands over the bus cable. How it all fits together is covered in KNX explained.
What the new actuators can do
Every channel has its own control button and a status LED. Both line up with the matching terminal, so you can see in the distribution board which output is switching. Whether manual operation is allowed is set in the ETS. It can also be influenced or locked via the bus.
The Xpress configuration in the ETS cuts down commissioning work. You assign the outputs to predefined use cases, and your own templates are possible too. Anyone who wants to set everything themselves picks “Individual” and gets the full set of parameters. From ETS 6.5.0 the actuators also support Smart Linking: links are created by drag and drop at function level, and the ETS creates the group addresses automatically. According to Gira, this works across manufacturers within the KNX standard.
All models support KNX Data Secure, and the device software can be updated. Firmware updates run through the Gira KNX Service app.
According to the Gira catalogue, each output works as a normally open or normally closed contact. On top of that come time functions such as staircase lighting with pre-warning, up to 64 scenes per output, disable and forced positions, an operating hours counter and status feedback. Eight internal logic functions are also on board, for example AND, OR and XOR with up to four inputs, or threshold switches.
All twelve versions
The 24-channel models take up 12 modules (TE) in the distribution board.
| Item no. | Model | Width |
|---|---|---|
| 5125 00 | Switch actuator 2-gang 10 A | 2 modules |
| 5126 00 | Switch actuator 4-gang 10 A | 4 modules |
| 5127 00 | Switch actuator 8-gang 10 A | 6 modules |
| 5128 00 | Switch actuator 12-gang 10 A | 8 modules |
| 5129 00 | Switch actuator 16-gang 10 A | 8 modules |
| 5130 00 | Switch actuator 24-gang 10 A | 12 modules |
| 5005 00 | Switch actuator 2-gang 16 A | 2 modules |
| 5006 00 | Switch actuator 4-gang 16 A | 4 modules |
| 5007 00 | Switch actuator 8-gang 16 A | 6 modules |
| 5008 00 | Switch actuator 12-gang 16 A | 8 modules |
| 5009 00 | Switch actuator 16-gang 16 A | 8 modules |
| 5010 00 | Switch actuator 24-gang 16 A | 12 modules |
The new actuators are not available on Amazon, you can find a comparable alternative here:
Last updated on 2026-11-18 / affiliate links / images from the Amazon Product Advertising API. Prices shown may have changed since then. All information without guarantee. * = affiliate link: if you order a product through such a link, we receive a commission from the seller. There are no extra costs for you.
Specifications
| 16 A range (5005 00 to 5010 00) | 10 A range (5125 00 to 5130 00) | |
|---|---|---|
| Medium | KNX TP | KNX TP |
| Switching voltage | AC 250 V | AC 250 V |
| Switching current AC1 | 16 A | 10 A |
| Fluorescent lamps | 16 AX (140 µF) | 10 AX (140 µF) |
| Max. inrush current | 235 A for 1000 µs | 170 A for 700 µs |
| Load per output | incandescent 1500 W, HV LED 400 W, motors 1150 VA | incandescent 1300 W, HV LED 200 W, motors 1150 VA |
| Adjacent outputs | max. 20 A combined | max. 20 A combined |
| Circuit protection | max. B16 | max. B16 |
| Terminals | screw terminals, max. 4 mm² or 2 × 2.5 mm² | screw terminals, max. 4 mm² or 2 × 2.5 mm² |
| Relays | bistable | bistable |
| Bus current | 5 to 18 mA (24-gang: 5 to 24 mA) | 5 to 18 mA (24-gang: 5 to 24 mA) |
| Ambient temperature | −5 to +45 °C | −5 to +45 °C |
| Security | KNX Data Secure | KNX Data Secure |
| ETS | from ETS 5.7.7 or ETS 6.3, Smart Linking from ETS 6.5.0 | from ETS 5.7.7 or ETS 6.3, Smart Linking from ETS 6.5.0 |
| In the box | actuator, KNX bus terminal, Secure Card, instructions | actuator, KNX bus terminal, Secure Card, instructions |
Who it is for
The actuators are powered by the bus voltage and mounted on the DIN rail in dry indoor rooms. They are planned and commissioned in the ETS. Homeowners mainly benefit indirectly: Xpress and Smart Linking shorten programming, and KNX Secure protects bus communication. If you are still deciding which system to use, KNX vs Loxone compares the two.
Sources are Gira’s press release and the data sheets in the Gira catalogue.