The bathroom should be warm in the morning, the bedroom cooler at night, and when a window is open in the living room, the heating should not fight against it. With KNX you control every room separately: a room temperature controller measures, calculates and sets the target, and a valve drive carries it out at the heating valve.
This article explains how KNX room-by-room heating control is built, which ways lead to the valve, what operating modes, control algorithms and underfloor heating mean in practice, and how to connect it all to Home Assistant. It is based on manuals and datasheets from MDT, Gira, JUNG, ABB, Zennio and Hager, the KNX support pages and the Home Assistant documentation, retrieved on 29 November 2026. For the basics of KNX, see KNX explained.
In short
- A room temperature controller calculates a control value for each room from the setpoint and the measured temperature. A heating actuator or a valve drive applies it at the valve.
- There are two routes: a heating actuator in the distribution board for thermal valve drives (24 or 230 V), or a drive with a bus connection directly at the valve.
- Typical operating modes are comfort, standby, night and frost/heat protection. The values depend on the device.
- Control comes as 2-point, PWM and continuous PI control. Thermal drives are slow, so the cycle time matters.
- Window and presence inputs, valve flushing and diagnostics are built into many devices.
- Home Assistant maps a room as a “climate” entity through group addresses.
How room-by-room control is built
The KNX model for heating and climate separates four tasks: an operating device supplies the desired setpoint and the room temperature. A “setpoint manager” turns these (optionally with window and presence status) into the effective setpoint. A heating controller calculates the valve position, and a valve actuator drives the valve. This is how the KNX Association describes it in its support documentation for the “KNX Virtual” simulation, which is based on these function blocks.
In real devices the tasks are often combined:
- Separate: A wall-mounted room temperature controller sends the control value over the bus to a heating actuator in the distribution board. MDT offers, for example, the SCN-RT1UP.01 controller and the “Smart 55/63” series.
- Integrated in the actuator: According to Gira, the heating actuator 2139 00 contains up to 12 room temperature controllers that work independently inside the actuator. The MDT heating actuator has an integrated temperature controller that drives the actuator directly from a temperature value, so no separate controller is needed. External controllers are also possible with Gira and MDT.
- Integrated in the drive: According to Gira, the KNX valve drive 3 (2176 00) contains a room temperature controller with a sensor.
According to ABB, a conventional thermostat with a switching output can be connected through a binary input (2-point or PWM).
Two routes to the valve
Heating actuator for thermal valve drives
This is the classic route for underfloor heating: the valve drives sit at the manifold, and the cables run to the heating actuator in the distribution board. According to ABB, an electrothermal drive contains an expansion element, for example a wax cartridge, which expands when voltage is applied and contracts when it is switched off. Opening or closing takes two to three minutes. Partial opening is achieved by pulse-width modulation. Drives are available for 230 V and 24 V, each either normally closed or normally open.
| Device | What the manufacturer says |
|---|---|
| MDT AKH-0400.02 / -0600.02 / -0800.02 | 4, 6 or 8 channels for electrothermal drives, 24 or 230 V AC. Each actuator runs either on 230 V or on 24 V, mixing is not permitted. Built-in short-circuit detection, and with 230 V also detection of a mains failure. |
| Gira 2139 00 | 6 electronic, silent outputs, up to 4 drives per output at 230 V or 2 drives at 24 V. Only electrothermal drives with ohmic behaviour. |
| JUNG 2336 REG HZ RHE | According to the 2016 product documentation, also 6 outputs with up to 4 (230 V) or 2 (24 V) drives each. |
| Zennio HeatingBOX | According to the manual, 4 or 8 outputs with a shared 230 V or 24 V supply, with messages for short circuit/overload and “all valves closed”. |
Gira advises connecting either 230 V or 24 V drives to one actuator, and using only drives with the same characteristic (normally closed or normally open) on each output.
Valve drive directly on the bus
For radiators (and manifolds with a thermostatic valve insert) there are drives with their own bus connection. According to a 2017 document, the Gira KNX valve drive 3 fits thermostatic valve inserts with an M30×1.5 connection and moves the valve proportionally between “closed” and “open”. Up to 30 drives are possible per line. The ABB valve drive ST/K 1.1 is an electromotive drive that receives its control value from a continuous KNX room temperature controller. We did not check whether these models are currently available.
According to the Hager catalogue page, the Hager valve drive TX502 is no longer supplied (“obsolete”).
Operating modes and setpoint shift
The controllers work with fixed operating modes. MDT, Gira and JUNG list:
- Comfort: The room is in use. With MDT the adjustable base comfort value lies between 18 and 25 °C (default 21 °C).
- Standby: The room is not in use during the day, and the temperature is lowered slightly. With MDT it is 0 to 10 K (default 2 K).
- Night: lowered clearly, for example at night. With MDT 0 to 10 K (default 3 K).
- Frost/heat protection: minimum or maximum temperature to protect the building.
An example from the MDT manual: with a base comfort of 21 °C, standby at −2 K gives 19 °C and night at −5 K gives 16 °C. These values are manual examples and can be set per device. In the MDT heating actuator, frost protection is fixed at 7 °C and heat protection at 35 °C. In the MDT room temperature controller SCN-RT1 you set them yourself (frost protection 3 to 12 °C, heat protection 24 to 40 °C).
With a setpoint shift you adjust the value by hand, for example with buttons on the controller. With MDT this works through 1 bit, 1 byte or 2 bytes, with a maximum shift of 0 to 10 K (default 3 K).
A “comfort extension” temporarily switches from night or frost protection back to comfort, time-limited by a button or through a presence object, for example from a KNX presence detector.
Control algorithms: 2-point, PWM and PI
| Control | How it works according to MDT |
|---|---|
| 2-point | Switches on when the temperature falls below the threshold and off when it rises above it. The hysteresis ranges from 0.5 to 5 K (default 2 K). Example: setpoint 21 °C, hysteresis 2 K, on at 20 °C, off at 22 °C. MDT gives 1.5 to 3 K as a guideline. Suitable when the control value has only two states, for example with an electrothermal valve. |
| PWM | The control value of the PI controller is converted into on and off pulses within a cycle time. 70 % with a 10-minute cycle means 7 minutes on, 3 minutes off. |
| Continuous PI control | The control value is sent as a 1-byte value (0 % = 0, 100 % = 255). Important are the proportional band (MDT: 1 to 8 K, default 3 K) and the reset time (15 to 210 minutes, default 120 minutes). |
MDT offers presets for heating systems: water heating 4 K and 120 minutes, underfloor heating 4 K and 150 minutes. According to MDT, free control parameters require “sufficient knowledge of control engineering”.
For thermal drives the cycle time is important. For an electrothermal drive, MDT gives about 2.3 minutes until it is fully open and advises against cycle times below 15 minutes. For underfloor heating MDT gives about 20 minutes. Zennio writes that the PWM period must not be shorter than the valve’s run time.
Underfloor heating
Underfloor heating reacts slowly. Its circuits therefore usually run with thermal drives and a longer reset time. MDT also recommends an additional stage, such as a radiator, to bridge a long heat-up phase.
- Normally closed or open: Gira, JUNG and Zennio allow both. With Gira and JUNG you set it per output. With MDT, “normally closed” is the default.
- Limiting floor temperature (Gira): The controller needs a floor temperature reading for this, for example from a sensor on an analogue input. The limit is 10 to 45 °C in the ETS, and the hysteresis is fixed at 1 K. Gira makes clear that this is not a safety-relevant protective function.
- Limiting flow temperature (MDT): Instead of the floor, MDT limits the flow temperature and uses a second sensor on the flow pipe for it. MDT gives protecting floor coverings as an example.
- Minimum floor temperature (MDT): With a floor sensor you can hold a minimum value, for example in the bathroom, so the floor does not get cold in the transition season.
Permissible maximum temperatures for floor coverings and heating up the screed are a matter for planning with the heating installer and the floor layer. We have not checked a source for them.
Heating and cooling
With surface heating you can also cool in summer. In the actuator, MDT distinguishes pure heating or cooling systems, 2-pipe systems (one circuit heats or cools, changeover needed) and 4-pipe systems (two separate circuits). The changeover runs through a 1-bit object: 1 means heating, 0 means cooling. A dead zone sits between the two setpoints. Example from the MDT manual: with a 3 K dead zone and a heating setpoint of 21 °C, cooling starts at 24 °C. The MDT actuator can also evaluate a dew point alarm to avoid condensation with surface cooling. We have not checked how it works in detail.
Window and presence as inputs
- MDT Smart: A window contact forces frost/heat protection when opened. The delay is adjustable (0 to 240 seconds, default 5 seconds), and so is the fallback time (1 to 24 hours, default 12 hours), which protects if the window stays open.
- Gira: The window status switches to frost/heat protection. A presence object, for example from a ceiling detector, activates comfort.
- ABB ST/K 1.1: two inputs for a window contact and presence at the drive.
Valve flushing and diagnostics
Valves that are not moved for a long time can seize or calcify. The manufacturers build in protective functions for this:
- MDT: According to the manual, the actuator fully opens all valves once in a fixed cycle every 6 days for 5 minutes.
- Gira and JUNG: Valve flushing runs cyclically (1 to 26 weeks) or by bus command. Optionally it is “intelligent” and flushes only if the valve was not moved enough in the cycle.
- ABB ST/K 1.1: a valve protection function, depending on the software version every 24 hours or every 7 days.
For diagnostics, Gira and JUNG report overload and short circuit per valve output as a 1-bit object. MDT provides a diagnostic text per channel and shows with the status LED whether the channel is active (slow blinking) or faulty (fast blinking). The MDT actuator also has an emergency mode: if control values stop arriving, the channel switches to a fixed value so that a controller failure does not lead to permanent heating at 100 %.
Setting up in the ETS
Parameters and communication objects come from the manufacturer’s product database. Names and values differ by device and application version, so the manual for your device applies. MDT lists the following parameter groups for its heating actuator as an example:
- General: device start-up time, thermal drive 24 V/230 V, summer/winter mode, heating/cooling system, seizure protection, behaviour after bus voltage recovery.
- Per channel: valve type (normally closed/open), lock function, emergency mode, PWM cycle, control value limits.
- Integrated controller: operating modes, setpoint shift, control parameters, comfort extension, dead zone.
More on the ETS is in ETS6 licences explained. The documents we read do not state which minimum ETS version a heating actuator requires. Check this in the manufacturer’s product database before buying.
KNX heating control and Home Assistant
Home Assistant connects KNX through the KNX integration (documentation, current version 2026.11.3). A room is created there as a “climate” entity, which the documentation describes as the interface to KNX thermostats and room controllers. You can set it up in the KNX panel or in YAML. All details on the connection are in Connecting KNX to Home Assistant.
- Required:
temperature_address(room temperature, DPT 9.001) andtarget_temperature_state_address(target temperature, DPT 9.001). - Setpoint shift:
setpoint_shift_addresswith DPT 6.010 or 9.002, depending onsetpoint_shift_mode. - Operating mode:
operation_mode_address(DPT 20.102) or separate 1-bit addresses for frost protection, night, comfort and standby. - Heating/cooling:
heat_cool_address(DPT 1.100), 0 means cooling, 1 heating. - Control value:
command_value_state_address(DPT 5.001). At 0 the entity counts as “idle” if noactive_state_addressis set.
Home Assistant only reads and writes group addresses. Which manufacturer object matches which address is not documented by Home Assistant, it follows from your ETS project.
Examples and prices
Manufacturers rarely state prices. The documents we read give no prices for MDT, JUNG, ABB and Zennio, and Gira’s price is a net price for the trade. Many KNX manufacturers sell through specialist channels (see KNX manufacturers at a glance).
One example of a KNX room controller with temperature control that is listed on Amazon (as of 29 November 2026) is the Theben iON 108. Amazon dispatches it, and a third-party seller sells it. Check price and availability, and whether the model fits your project:
Last updated on 2026-11-29 / affiliate links / images from the Amazon Product Advertising API. Prices shown may have changed since then. All information without guarantee. * = affiliate link: if you order a product through such a link, we receive a commission from the seller. There are no extra costs for you.
What we cannot confirm
- Savings in euros or kilowatt hours from room-by-room control, and costs per room.
- Permissible floor temperatures and heating up the screed.
- Hydraulic balancing, heating curve and connection to a heat pump.
- Details on Theben, Siemens, Hager (except the catalogue entry for the TX502) and Weinzierl, because the documents were not reachable or not read.
- Which valve fits which radiator. Only the M30×1.5 connection of the Gira drive is documented.
- The minimum ETS version and operation in ETS 6 for heating actuators.
The MDT manuals date from 2019 to 2022, and the Gira document on the direct drive from 2017. We did not check whether newer versions exist.
Frequently asked questions
Do I need a room temperature controller and a heating actuator?
Not always. According to the manufacturers, the MDT heating actuator and the Gira 2139 00 have controllers built in. Alternatively, a wall controller regulates and sends the control value to the actuator.
Can I mix radiators and underfloor heating?
Yes, every circuit has its own valve and receives a control value. Which control parameters fit depends on the system. MDT offers separate presets for water heating and underfloor heating.
How long does a thermal valve drive take?
According to ABB, opening or closing takes two to three minutes.
What happens if the controller fails?
With the MDT actuator the channel switches to a fixed emergency value after an adjustable time without a control value. Gira and JUNG also offer control value monitoring with emergency mode.
Can I control the heating in Home Assistant?
Yes, through the KNX integration as a climate entity with group addresses for temperature, target temperature, operating mode and control value.
More on planning a new build is in Planning KNX in a new build. You can find all articles on KNX and Loxone in the KNX & Loxone category.