In a renovation, running a cable to the switch is often no longer an option. For such cases there is KNX RF: KNX over radio. The devices are programmed with the ETS as usual, only the cable is gone.
This article explains how KNX RF works, which generations exist, why you need a media coupler and where the limits are. It is based on the KNX Association, manufacturer pages, data sheets and price lists retrieved on 26 November 2026. How KNX works in general is covered in KNX explained.
In short
- According to the KNX Association, KNX RF uses the 868 MHz band instead of the twisted-pair cable. Device logic and the ETS stay the same.
- Gira gives 868.3 MHz as the centre frequency. According to Gira, each device may only transmit 1 % of the time (RF1.R).
- There are several generations: RF 1.1, RF Ready, RF Multi and RF Multi SLE. The newer ones are backward compatible with RF Ready.
- A media coupler links radio to a wired installation. It can act as an area, line or segment coupler.
- Manufacturers quote about 100 metres in open field. No manufacturer gives a binding range inside a building.
- KNX Secure is possible over radio and is intended for RF Multi. Without Secure the transmission is unencrypted.
- All prices below are manufacturers’ list prices excluding VAT.
How does KNX RF work?
In KNX, sensors and actuators exchange telegrams. Normally they travel over the bus cable (twisted pair, TP). KNX RF carries the same principle over radio. The KNX Association puts it this way: KNX RF works in the 868 MHz band instead of on the cable, while device logic and the ETS stay the same.
Radio is a shared medium. Gira points out that the band is shared with other radio services. That is why there are rules:
- Transmission time is limited. For RF1.R it is 1 % per device according to Gira, i.e. at most 0.6 seconds per minute.
- Before sending, the device listens to the channel (listen before talk) and waits a random time.
- According to Gira, transmit power is 0.5 to 25 mW and the data rate is 16.384 kbit/s.
The devices are programmed in the ETS as usual (see ETS6 licence explained). The ETS creates a domain address that is written to the device during download. Radio devices work in what is called S-mode, i.e. with ETS configuration.
The generations: RF 1.1, Ready, Multi and SLE
In a guest article by ise, the KNX Association lists this order: KNX RF 1.1, then KNX RF Ready, followed by KNX RF Multi and now KNX RF Multi SLE.
| Feature | RF Ready | RF Multi |
|---|---|---|
| Frequencies | 868.3 MHz only | four frequencies: 868.3 / 868.95 / 869.525 / 869.85 MHz |
| Acknowledgement | none | Fast Ack, channel change on interference |
| Battery devices | semi-bidirectional | bidirectional, reachable by the ETS at any time |
| ETS | from ETS 5 | from ETS 6 |
According to the KNX Association, RF Multi has a fast channel for mains-powered devices and a slow channel (SLE) for battery devices. SLE is currently the only way to run battery-powered KNX RF Multi devices efficiently. A mains-powered coupler lets Ready, Fast and SLE devices work together.
Gira is not consistent about the number of channels: its web page says up to four, a technical information PDF says up to five. The data sheet and ise show four frequencies, so we stick with four.
The name “RF+” comes from MDT for its own radio line. We did not find a definition of it by the KNX Association.
The media coupler: bridge between cable and radio
To add radio devices to an existing KNX installation you need a TP/RF media coupler. It translates between cable and radio. Several models exist:
| Model | Key data according to the manufacturer |
|---|---|
| Gira RF Multi/TP media coupler (5114 00) | RF1.R and RF1.M, repeater, security proxy, Secure card included, open field about 100 m |
| JUNG KNX RF media coupler MK 100 RF | area/line coupler, repeater, Data Secure from V01, segment coupler from V02, open field typically 100 m |
| MDT RF+ wireless line coupler flush-mount Secure (RF-LK001.03S) | line coupler, Data Secure, security proxy, segment coupler from ETS 6, flush-mount |
| Zennio ZMCoup RF 868 | connects TP lines to KNX RF, extended frames, ETS 5 and 6 |
| Weinzierl KNX RF-TP Coupler 670 | 24 channels, also usable as retransmitter |
According to Gira, the coupler can also serve as a repeater. As a rule one media coupler per line is enough, further ones are only meant as repeaters. Their placement in the room matters.
Devices: push buttons, actuators, thermostats
Radio versions exist for the typical retrofit jobs. Examples from the manufacturers’ lists:
| Device | Model |
|---|---|
| MDT RF+ wireless push button light 55 basic, one rocker | RF-TAL55B102.01S |
| MDT RF+ wireless glass push button plus, 4-gang | RF-GTT4W.01 |
| MDT RF+ window contact, Secure | RF-FKWS.01S |
| MDT RF+ radiator thermostat, Secure, alkaline battery | RF-HVA1DAA.01S |
| Gira RF hand transmitter, 4-gang | 5124 00 |
| Gira RF Multi actuator for radiators | 5115 00 |
| Gira RF Multi data interface (USB stick) | 5121 00 |
Source: MDT price list 10/2026 and Gira data sheets 11/26. More on Gira in the Gira product overview. Which other manufacturers exist is covered in KNX manufacturers at a glance.
Battery and energy
For battery devices, runtime matters:
- According to its data sheet, the Gira RF Multi radiator actuator typically lasts two heating seasons on two AA batteries.
- The KNX Association gives up to two years under typical conditions for the RF Multi radiator thermostat from ise.
- MDT quotes up to 10 years of battery life across the RF+ range. That is a manufacturer figure and depends on the device and its use.
A battery-free example is the ZF push button module, which according to the manufacturer gains its energy from the movement of the button. The announcement dates from 2018. We have not checked whether it is still sold.
Range and limits
Gira, JUNG and ABB quote about 100 metres in open field. Gira explicitly says it cannot give a binding range inside buildings. The signal is attenuated by, among other things:
- reinforced concrete,
- metallised insulation,
- plasterboard with conductive fibres (attenuation up to 95 %, according to Gira),
- mounting close to the floor.
Gira recommends a mounting height of 1.05 to 1.50 metres. Repeaters can extend the range. According to an ABB webinar, up to two repeaters are possible, also across several floors.
Further limits according to the manufacturers’ documentation:
- The band is shared with other radio services.
- Neighbouring KNX RF lines or two couplers out of range of each other can cause telegrams to collide.
- A perfectly simultaneous reaction to broadcast or read telegrams is not possible.
- With Ready battery devices the receiver is off in power-saving mode. With Gira, toggle buttons may then need two presses, and power-saving mode must be ended before the ETS download.
KNX Secure over radio
Radio is an open medium. The KNX Association writes that KNX RF devices can use KNX Data Secure with AES-128 CCM. With RF it is normal for devices to support Secure, while devices on the cable may keep running without it. The media coupler provides a security proxy for this. It translates between devices with and without Secure. According to ise, ETS 6 configures it automatically.
Without Secure commissioning, KNX RF is unencrypted, and ise explicitly recommends Secure. How Secure works is explained in KNX Secure explained.
Commissioning in the ETS
- ETS version: RF Ready runs from ETS 5, RF Multi from ETS 6. Individual devices need a newer version, the Gira radiator actuator for example ETS 6.2. Check the data sheet for each device.
- Access: via a KNX RF USB interface (for example Gira 5121 00 or Weinzierl 340) or via a TP or IP interface with an existing media coupler.
- RF Multi: Gira mentions remote maintenance without pressing the programming button again. SLE devices stay reachable for the ETS.
An IP interface helps if the wired line next to the radio line should be reachable over IP. According to the Gira system description, the IP connection can reach the RF line via a media coupler and an IP router or interface. More on Home Assistant and IP interfaces in How to connect KNX to Home Assistant.
When KNX RF makes sense
KNX radio fits where no cable can be added: in old buildings, during conversions, on glass walls or for an extra push button. In a new build, the bus cable can instead be planned into the shell (see KNX in a new build). More options without the ETS are shown in KNX without ETS. How KNX works together with Matter is covered in KNX and Matter.
We do not give a cost estimate for a whole house because there is no sourced figure for it. The list prices of individual devices are in the manufacturers’ lists.
One device for your project
For ETS commissioning and the link to a wired line, an IP interface helps. One example on Amazon is the Gira IP interface (item no. 216800). It is not a radio device but the access to the wired line to which a media coupler is connected. Check before buying that it suits your project.
Last updated on 2026-11-24 / affiliate links / images from the Amazon Product Advertising API. Prices shown may have changed since then. All information without guarantee. * = affiliate link: if you order a product through such a link, we receive a commission from the seller. There are no extra costs for you.
Frequently asked questions
Is KNX RF less secure than wired KNX?
Radio is an open medium, which is why KNX provides Secure for RF. Without Secure the transmission is unencrypted. With Secure and a security proxy, both worlds can be mixed.
How far does KNX RF reach?
Manufacturers quote about 100 metres in open field. Inside a building it depends on walls, insulation and mounting. No manufacturer gives a binding figure.
Do I need wired KNX to use radio?
Not necessarily. But you need an access for the ETS, for example a KNX RF USB stick. To connect to a wired installation you need a media coupler.
Can I mix devices from different manufacturers?
Weinzierl, for example, names compatibility with several manufacturers for its coupler. Still, check for each device which RF generation and ETS version it needs.
All articles on KNX and Loxone are in the KNX & Loxone category.