The hallway lights up when you walk in, and the office light stays on as long as you sit at the desk: in a KNX installation, a presence detector often takes care of that. It connects directly to the KNX bus and reports motion, presence and usually brightness to other devices.
This article explains how a KNX presence detector differs from a simple motion detector, which functions it offers, what to watch for when mounting it and how to set it up in the ETS. It is based on manufacturer datasheets, manuals and product pages as well as the Home Assistant documentation, retrieved on 28 November 2026. For the basics of KNX, see KNX explained.
In short
- According to JUNG, a presence detector evaluates even the smallest movements and keeps measuring brightness while the light is already on. A “ceiling motion detector” is rather meant for passage areas.
- The sensor technology differs: PIR reacts to heat radiation, while RF (radar) and ultrasonic work with emitted signals.
- Typical functions are a brightness threshold, delay time, fully and semi-automatic mode, constant light control and channels for lighting, HVAC and alerts.
- The mounting height depends on the device. The datasheets range from 2 to 12 m, with tighter limits for fine movements.
- The detector sits directly on the bus. Parameters and communication objects come from the manufacturer’s product database in the ETS.
- The standard detectors from JUNG and Gira we checked are explicitly not meant for alarm systems.
Motion detector or presence detector?
The terms are not a KNX standard. The KNX Association has no uniform definition; the distinction comes from manufacturers. JUNG describes it in the product documentation for model 3361:
- Ceiling motion detector: usually for passage areas. The light stays on until nobody is in the area any more.
- Presence detector: for rooms where people stay longer, such as a workplace or bathroom. It can evaluate the smallest movements. In brightness-dependent mode it keeps measuring brightness while the light is on and can, for example, switch off when daylight comes in.
MDT and Steinel say something similar: according to the manufacturers, the detectors pick up even the smallest movements, such as typing on a keyboard, so the light does not switch off unnecessarily.
Which sensor technology is inside?
Steinel explains the three common principles on its presence detector page:
| Technology | How it works according to the manufacturer | Good to know |
|---|---|---|
| PIR (infrared) | Detects the heat radiation emitted by people. | According to Steinel the first choice for large radii. Siemens writes that the sensor reacts to temperature differences: the smaller the difference to the surroundings, the worse the movement is detected. |
| RF (radar, Doppler) | Sends out signals and evaluates changes in the echo. | According to Steinel, the signals penetrate glass, wood and lightweight walls. |
| Ultrasonic | Sound waves fill the room, movement is detected even without line of sight. | Does not penetrate thin walls, very sensitive according to Steinel. |
Most ceiling detectors in the datasheets we read are PIR devices. The MDT SCN-P360 uses up to four pyro sensors, the Gira Presence Detector Mini one PIR sensor (360°), and JUNG lists 3 PIR sectors of 120° for its standard detector. The Steinel True Presence 079451, by contrast, uses RF technology (7.2 GHz) and, according to the manufacturer, even detects breathing movements.
What a KNX presence detector can do
Brightness and threshold
Almost every detector has a light sensor. MDT lists 5 to 1000 lux, Gira 10 to 2000 lx for the Mini. You set a threshold: if it is brighter, the light stays off. The detector also sends the measured brightness value to the bus so other devices can use it.
Delay time
This is the time from the last detected movement until the light switches off. With MDT, every new detection restarts it. For the Hager TCC520E, the on-time ranges from 60 seconds to 60 minutes according to the catalogue. MDT lets you set the delay separately for day and night.
Fully and semi-automatic mode
- Fully automatic: Any detected presence switches the light on, and it goes off again after the delay time.
- Semi-automatic: You switch on by hand, for example with a push button. Switching off happens automatically after the delay time.
That is how MDT describes it. Hager lists the modes “automatic, semi-automatic, test” for its TCC520E, Gira “auto/manual on/off” for the Mini.
Constant light control
The K models from MDT (for example SCN-P360K3.03) control up to three light bands, namely wall, centre and window, so that the brightness in the room stays constant, according to the manufacturer. Sunlight is compensated. The detector sends a dimming value from 0 to 100 percent. In the older ABB Busch-Präsenz tech manual (2011), there was a constant light switch for on and off only and a DualLINE variant that can also dim.
Channels for lighting, HVAC and alerts
The MDT manual describes up to four light channels, one HVAC channel and one alarm or alert channel. The HVAC channel is the interface to heating, ventilation and air conditioning: according to MDT it switches when at least one movement was detected in 1 to 32 consecutive observation windows. MDT gives demand-based control of ventilation as an example.
Additional sensors
Some detectors measure more than motion. The Siemens devices UP 258D31, D41 and D51 provide temperature, the D41 adds humidity and dew point, the D51 also CO2. The Zennio Presentia C MultiSensor measures temperature, humidity and CO2 and includes a thermostat. The Gira Mini also measures temperature and brightness.
Security on the bus
According to its datasheet, the Gira Mini is compatible with KNX Data Secure, and the Zennio ZPDCMS supports it as well. For the Steinel 079451, the product overview says “KNX Secure: No”. More in KNX Secure explained.
Important: JUNG writes that model 3361 is not suitable for burglar alarm or alarm technology. Gira says the Mini is not suitable for alarm messages in VdS-compliant alarm systems. MDT does offer an alarm or alert channel, but that does not make a standard detector a replacement for a certified alarm system.
Mounting: height, detection area, installation type
There is no single correct mounting height. It depends on the device, as the datasheets show:
| Detector | Mounting height per manufacturer | Detection (manufacturer data) |
|---|---|---|
| MDT SCN-P360D3.03 / K3.03 | 2 to 4 m, switch box | Motion 11 m, presence 5 m (at 4 m height), 360° |
| Gira Presence Detector Mini Standard | 2.20 to 5.0 m | Ø approx. 12 m at 3 m height, presence 4.2 m |
| JUNG Standard 3361 | 2.20 to 5.0 m, as a presence detector not above 3.5 m | Ø 20 m at 3 m height (tangential) |
| Hager TCC520E | recommended 2.5 to 3.5 m, maximum 4 m | frontal 7 m, sideways 8 m (at 2.5 m) |
| Steinel True Presence KNX 079451 | 2 to 12 m, optimal 2.8 m | Ø 15 m motion/presence, Ø 9 m True Presence (only up to 4 m height) |
| Siemens UP 258D31/D41/D51 | optimal 3 m, calibrate above that | Presence up to 64 m², motion up to 400 m² |
Datasheets: MDT, Gira, JUNG, Hager, Steinel, Siemens (the documents are in German).
Two things stand out. First, the detection area grows with height, but sensitivity drops, as JUNG describes. Second, height matters for fine movements at a desk: JUNG gives at most 3.5 m for fine detection. In the older ABB manual, 4 to 5 m is no longer suitable for pure desk work.
Installation type and connection
- Box or clips: The MDT sits in the switch box. The Gira Mini is clipped into suspended ceilings; on solid ceilings it goes into a device box to DIN 49073 (accessory), surface mounting is also possible with an accessory. JUNG and Siemens use flush-mounted device boxes or a surface-mounted housing.
- Bus connection: The ceiling detectors we read connect directly to the KNX bus and have the bus coupler built in. The Zennio detector needs no external auxiliary voltage according to its datasheet.
- Indoors or outdoors: The MDT SCN-P360 is meant for dry indoor rooms (IP 20). The Gira Mini is IP44 and, according to its datasheet, may be used in wet rooms and outdoors.
- Never on 230 V: The Steinel detector is for extra-low voltage only and must never be connected to 230 V. A qualified electrician should always do the installation.
Where the detector should not go
- Not in airflow or near heat: JUNG names heaters, ventilation, air conditioning and cooling lamps as sources of interference, Siemens adds fan heaters, fans and draughts. The only concrete distances in our sources come from an older ABB manual (2011): lamps closer than 1.5 m interfere, radiators beyond 1.5 m do not. For your device, the datasheet applies.
- Not shadowed: Partitions, large plants, shelves or suspended luminaires reduce the detection area (Siemens). According to Siemens, people behind walls and glass are not detected.
- Not in the sun: Avoid direct sunlight on the sensor window (JUNG). No direct sun or artificial light should fall on the light guide of the brightness sensor.
- With constant light control: MDT requires at least 60 cm distance to the nearest luminaire, and the detector sits in line with the middle group of luminaires.
The KNX Association’s general guide to motion detectors recommends about 2 to 2.5 m for wall and corner detectors and also says: do not mount behind large furniture, and with infrared sensors avoid heat sources and rooms that heat up. That does not apply to ceiling detectors with different datasheet values.
Setting up in the ETS
What a KNX device can do is described in the manufacturer’s product database. You import it into the ETS or load it through the online catalogue. It determines parameters and communication objects. The KNX Association support pages on this are written for ETS 5 and marked as deprecated, but the basic principle still applies.
A typical sequence, here according to the MDT manual:
- Assign the physical address.
- Load the application program in the ETS.
- When the ETS asks for it, press the programming button on the detector. The red LED goes out after successful programming.
What you typically set
- Sensitivity (MDT: 10 steps, JUNG: per PIR sector in the ETS and additionally with a potentiometer on the device).
- Brightness threshold, delay time, operating mode.
- Communication objects that you link to group addresses, for example “Output switch” (1 bit) for the light or “Brightness measured value” (2 bytes).
- Lock objects, for example to block motion detection temporarily.
Important: the default parameter values also decide which objects are visible. If you change a parameter, objects can disappear. Group addresses already linked are then lost, and the ETS warns you. Object numbers also differ between application versions, so always check the manual for your version.
More about the ETS and its licences in ETS6 explained.
Typical setting mistakes
- The light switches itself on again: Switching luminaires in the detection field on and off can trigger movement through the change in heat radiation. JUNG recommends feeding the switching state of the luminaires to the 1-bit object “PIR sensor lock”. Detection is then suppressed for an adjustable time.
- False triggers in large rooms: If false triggers in the far range happen often, JUNG advises lowering the basic sensitivity. Air movement in the outer area is then suppressed, and body-heat movement in the near range is hardly affected.
- Detector mounted too high: For fine movements, detection drops with height (JUNG, ABB, Siemens, see above).
- Direct light on the sensor: It disturbs constant light control (MDT 60 cm, Siemens “avoid direct artificial light”).
- Night light and brightness: With MDT, the brightness value is not evaluated while the white night light is active.
- Delay caused by filters: The MDT motion filter hides very short movements, for example from draughts. A movement then has to be detected longer before it switches.
- Skipping the walk test: Gira and JUNG offer a walk test to check detection and sources of interference. Use it after mounting.
Presence detectors and Home Assistant
Home Assistant integrates KNX through its KNX integration (documentation, current version 2026.11.3). A motion detector is created there as a binary sensor. According to the documentation, binary sensors are read-only. You need the group address of the presence or motion object (1 bit, DPT 1) as state_address. Options include reset_after, invert and sync_state.
Brightness runs as a 2-byte value (DPT 9.004), temperature as DPT 9.001, humidity as DPT 9.007 and CO2 as DPT 9.008; they are listed in the Home Assistant table of value types. Home Assistant does not document which manufacturer object maps to which entity; that follows from your ETS project. For a stable connection, Home Assistant recommends a certified KNX IP interface or IP router. The integration supports KNX Secure through an imported keyring file. All details in Connecting KNX to Home Assistant.
Example from Amazon
Manufacturers rarely publish prices, and several KNX manufacturers sell through the trade channel (see KNX manufacturers at a glance). One example that fits the topic and is listed on Amazon with sale and dispatch by Amazon (as of 28 November 2026) is the Gira Komfort KNX 210602 presence detector. Stock was low that day. Check availability and whether the model suits your installation.
Last updated on 2026-11-27 / affiliate links / images from the Amazon Product Advertising API. Prices shown may have changed since then. All information without guarantee. * = affiliate link: if you order a product through such a link, we receive a commission from the seller. There are no extra costs for you.
What we cannot confirm
- A general mounting height for all detectors and a general minimum distance to heating or ventilation. Both are only in the datasheet of the device.
- Savings in money or kilowatt hours from presence detectors.
- Prices for MDT, JUNG, Steinel, Siemens, Zennio and ABB.
- The current ETS 6 interface in detail, because the KNX support pages describe ETS 5.
Frequently asked questions
What is the difference between a motion detector and a presence detector in KNX?
There is no KNX standard for it. According to JUNG, a ceiling motion detector is meant for passage areas, a presence detector for rooms where people stay longer. It evaluates the smallest movements and measures brightness even while the light is on.
How high do I mount a KNX presence detector?
That depends on the device. The datasheets list, for example, 2 to 4 m (MDT), 2.5 to 3.5 m recommended (Hager) or 2.20 to 5 m (Gira, JUNG). For fine movements JUNG gives at most 3.5 m.
Does the presence detector need its own mains connection?
The ceiling detectors we read connect directly to the KNX bus and have the bus coupler built in. Zennio states explicitly that its detector needs no external auxiliary voltage. For the Steinel detector: never connect it to 230 V.
Can I use a presence detector for the alarm system?
JUNG and Gira rule this out for the models named. They are not meant for burglar alarm or VdS alarm technology.
Can I integrate the detector into Home Assistant?
Yes, through the KNX integration as a binary sensor with the group address of the presence or motion object.
For planning in a new build, see Planning KNX in a new build. All articles on KNX and Loxone are in the KNX & Loxone section.